High-precision electrical test equipment Kvtester Zc-206 Transformer sweep frequency response analysis Winding deformation displacement distortion tester

DescriptionTransformer winding deformation tester quantizing windings parameter changes in different frequency domain, according variance, range, extent and trend of frequency response, to decide deformed extent of the windings, and then decide if the transformer was badly damaged or needed major repairs according the testing re

Featured Products

Description

High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester

Transformer winding deformation tester quantizing windings parameter changes in different frequency domain, according variance, range, extent and trend of frequency response, to decide deformed extent of the windings, and then decide if the transformer was badly damaged or needed major repairs according the testing results. The device with compact structure, it is easy to operate.

Features

1. Use high-speed, high integration microprocessor to sample and control.

2. Use USB to connect the notebook PC and device.

3. Use wireless blue-tooth interface to communicate the notebook PC and device. The high-speed microprocessor integrated with device, need not move the computer during the field test.

4. Hardware cassette mechanism adopts DDS (from America), can correctly detect the breakdown :distortion, swell, shift, tilt, inter-turn short circuit deformation and contacting short circuit inter-phase.

5. High resolution dB to test, dual channel, 16 bit A/D sampling (the wave from curve will change obviously if change the tapping switch during the field tests. )

6. The software can adjust the output signal range, the maximum amplitude peak±10V.

7. The computer automatically generating the test results to be Word document.

8. Use precision , high stability components, repeat to test , the measurement repetition rate >99.5%.

9. Finished circuit boards, the surface with special treatment.

10. The device with two measurement system: linear scan and sectional scan.

11. Amplitude-frequency characteristic complies the national technical specifications.

12. Test data automatic analysis system, horizontal compare the similarity of A,B ,C, the results as below:
      1.conformance is very good
      2.conformance is good
      3. conformance is bad
      4.serious deformation
      Vertical compare A-A,B-B,C-C, obtain the original data to compare the winding deformation with the test data in the same phase, the results as below:
      1.normal
      2.slight deformation
      3.moderate deformation
      4.serious deformation

13. Automatically generating Word document,convenient for customers to save and print.
14. Totally meet the technique conditions of DL/T911-2004:Survey of Frequency Response Analysis on Winding Deformation of Transformers.

Product Parameters

Scanning mode

linear scan distribution

Sweep frequency measurement range

(1kHz)~(2MHz) 2000 Sweep frequency point; resolution ratio 1kHz range

Measurement accuracy

0.1dB

Scanning frequency accuracy

<0.01%

Scanning measurement range

(0.5kHz)~(1MHz)      2000 Sweep frequency

(0.5kHz)~(10kHz)    resolution ratio 0.02kHz

(10kHz)~(100kHz)    resolution ratio 0.02kHz

(100kHz)~(500kHz)    resolution ratio 1 kHz

(500kHz)~(1000kHz)    resolution ratio 1 kHz


High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
High Accuracy Electrical Testing Equipment Kvtester Zc-206 Transformer Sweep Frequency Response Analysis Winding Deformation Displacement Distortion Tester
 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours