Gdgs Transformer Power Factor Tester Tan Delta Tester

GDGS Transformer Power Factor Tester Tan Delta Tester Introduction:GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is an integrated structure, there is a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor bu

Featured Products

GDGS Transformer Power Factor Tester Tan Delta Tester Gdgs Transformer Power Factor Tester Tan Delta Tester

Introduction:

  • GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is an integrated structure, there is a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor built-in;

  • It can also supply high voltage source for testing.

  • Frequency can be changed to 50Hz, 47.5Hz\52.5Hz,45Hz\55Hz, 60Hz, 57.5Hz\62.5Hz, 55Hz\65Hz; thus, it can avoid interference of power frequency;

  • It can also use generator as power supply;

  • If equipped with a insulation oil vessel and a temperature detector, it can also measure tan delta of insulation oil;


Specifications:
 
No.ItemGDGS Transformer Insulation Power Factor Testing Equipment
1AccuracyCx±(reading×1%+1pF)
PF±(reading×1%+0.00040)
2Interference RatioInterference current is no more than 2 times of test current
3Capacitance RangeInternal HV:  3pF~60000pF / 10kV,60pF~1uF/0.5kV
External HV  3pF~0.3uF/10kV
Resolution  0.0001pF, 4 digital
4PF RangeNo limit, Resolution 0.001%, C/L/R specimen test
5Input current range10μA~1A
6Internal HV0.5~10kV / 200mA (max)
7HV AdjustRise or fall smoothly
8HV Accuracy±(reading×1%+10V) Resolving 1V
9Frequency select60Hz single point, locked 55Hz/65Hz double point, locked
10Test Time40S typical
11Power Supply180V~270V 50Hz/60Hz auto
12Operating Temperature0ºC~60ºC
13Storage Temperature-20ºC~60ºC
14Humidity<90%


Working Principle:
 
  • In the AC voltage, the dielectric to consume part of the energy, this part of the energy will be converted to heat energy loss. This energy loss is called dielectric loss.
  • When AC voltage is applied on the dielectric, the dielectric between voltage and current in phase difference angle psi, delta psi is called the dielectric loss angle tangent TG delta delta is called dielectric loss tangent. TG delta value is used to measure dielectric loss parameters. The instrument measuring circuit includes a standard circuit (Cn) and a test loop (Cx), as shown in Figure 2 - 1. The standard circuit is composed of a built-in high stability standard capacitor and a measuring circuit. Measurement line sampling resistor with pre amplifier and A/D converter. By measuring circuit are respectively measured by standard test and loop current loop current amplitude and phase difference, then the digital signal processor using digital real-time acquisition method, obtained through vector operation test of capacitance and dielectric loss tangent value. The anti-interference measures have been adopted in the instrument to ensure the accurate measurement under the interference of external electric field.
Gdgs Transformer Power Factor Tester Tan Delta Tester


Gdgs Transformer Power Factor Tester Tan Delta Tester
Gdgs Transformer Power Factor Tester Tan Delta Tester

Gdgs Transformer Power Factor Tester Tan Delta Tester