GDKC-12A High Voltage Circuit Breaker Transformer Tester

GDKC-12A High Voltage Circuit Breaker Tester Transformer Test Device High voltage circuit breaker is one of the most important control equipment in the power system. GDKC-12A is used to test the dynamic charact

Featured Products

GDKC-12A High Voltage Circuit Breaker Tester Transformer Test Device
 

High voltage circuit breaker is one of the most important control equipment in the power system. 

GDKC-12A is used to test the dynamic characteristics of high voltage circuit breaker. It is easy to operate, with high accuracy. 




Features
  • Time: the open/close time, in phase synchronization, phase-to-phase synchronization of 12contacts.
  • Reclose: close-open, open-close, open-close-open time for each contact.
  • Bounce: Close bounce time, times, process and waveform of each contacts.
  • Velocity: Velocity at contact touch, maximum speed, time-range characteristic curve. 
  • Travel: Total travel, open travel, over travel, travel overshoot, bounce amplitude.
  • Current: open/close current, current waveform diagram of the open/close coil.
  • Operation voltage: built-in DC30~250V/20A digital, adjustable power source of breaker, automatically complete LV action test of circuit breaker and measure action voltage value of circuit breaker. 
  • It is suitable to test the mechanism parameters of all types of SF6 circuit breaker, GIS combination electric equipment, vacuum circuit breaker, oil circuit breaker.
  • Strong anti-interfere ability. It also can easily test and accurately measure even interbus is live in 500kV substation.
  • With universal velocity sensor(optional), linear velocity sensor, rotary sensor, easy to install.
  • Only one time action to obtain all data and corresponding waveform of breaker mechanism test.
  • Storage test data, built-in real-time clock, which is convenient to save test date and time.
  • LCD screen display, with contrast adjustment and power-off memory.
  • Built-in printer, to get all data and diagram at any time quickly.



Specification


1.1 Using Environments
Input Power: 220V± 10% 50Hz± 10% Air Pressure: 86~106kpa
Temperature: -10~40 degree
Humidity: 80%RH

1.2 Safety Performance
Insulation Resistance>2MΩ
Dielectric Strength: Chassis can withstand voltage 1.5kv and power frequency for 1 minute without flash-over and arcing.

1.3 The Basic Parameters

A. Time: Range 25000.0ms resolution 0.01ms
Error 250ms 0.01ms ± 1digit
         2500ms 0.1ms ± 1digit
         25000ms 1ms ± 1digit
Same period
B. Velocity: Range 20.00m / s resolution 0.01m / s
Error 0-2m / s ± 0.1m / s ± 1digit
Above 2ms ± 0.2m / s ± 1 digit

C.Range: 
 RangeResolutionError
Vacuum breaker50.0mm0.1mm 
0.1±1digit
SF6 circuit breaker300.0mm1mm
Oil circuit breaker600.0mm

D. Current: Range 20.00A resolution 0.01A
E. Output power: DC0 ~ 300V digital adjustable / 20A (instantaneous work), resolution 1V.
F. Dimensions: 360mm (L) × 280mm (W) × 300mm (H)
G. Weight: 10kg







GDKC-12A High Voltage Circuit Breaker Transformer Tester

GDKC-12A High Voltage Circuit Breaker Transformer Tester