Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester
Introduction:
- GDGS Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations.
- Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester can also be used in laboratory for high accurate test. The set is whole in one designed: including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits.
- It's also using frequency shift technology, FFT (Fast Fourier Transform algorithm) and digital filtering. When started, it's running automatically and then outputs the results on LCD display and prints the results automatically.
Specifications:
No. | Item Name | Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester | ||
1 | Use conditions | -15ºC∽40ºC | RH<80% | |
2 | Anti-interference | Frequency conversion | ||
3 | Power | AC 220V±10% |
| |
4 | High output | 0.5KV∽10KV | Every 0.1kV | |
Precision | 2% | |||
Maximum current | 200mA | |||
Capacity | 2000VA | |||
5 | Self-excited power | AC 0V∽50V/15A | 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency | |
6 | Resolving power | tgδ: 0.001% | Cx: 0.001pF | |
7 | Precision | △tgδ:±(Reading*1.0%+0.040%) | ||
△C x :±(Reading*1.0%+1.00PF) | ||||
8 | measuring range | tgδ | Unlimited | |
C x | 15pF < Cx < 300nF | |||
10KV | Cx < 60 nF | |||
5KV | Cx < 150 nF | |||
1KV | Cx < 300 nF | |||
CVT test | Cx < 300 nF | |||
9 | CVT range | 10∽10000 | ||
accuracy | 0.1% | |||
Resolving power | 0.01 | |||
10 | Exterior dimension | 350(L)×270(W)×270(H) | ||
11 | Memory size | The 200 group supports U disk data storage | ||
12 | Weight | 28 Kg |
Package List:
- The GDGS Transformer Insulation Power Factor Tester;
- User's manual and quality certification;
- Test cable;
- Main lead;
- Additional color ribbon, paper roll and fuse;