Single Phase 10A DC resistance tester transformer winding resistance tester
- INTRODUCTION:
It is applied to measure the DC resistance of inductance circuit such as power transformer coil, current transformer coil and so on.
Also the tester could be applied to measure the cable resistance in 4-wire mode.
- FEATURES:
- It is suitable for large-scale transformer above 240MVA in temperature rising tests.
- 840MVA transformer low-voltage direct-resistance tester completed within 2 minutes and the data is stable and accurate.
- Dual-channel shows the measurement data at the same time.
- Each interval of 60 seconds automatically print data.
- Equipped with temperature conversion software, curve waveforms.
- SPECIFICATIONS:
Single Phase 10A DC resistance tester transformer winding resistance tester
PARAMETER | GDZC-10 |
Phase | Single |
Max. test current | 10A |
Measuring range | 1Ω~1000Ω(20mA) 100mΩ~100Ω(200mA) 10mΩ~20Ω(1A) 4mΩ~8Ω(2.5A) 1mΩ~2Ω(10A) |
Resolution | 1μΩ |
Max. error | 0.2%RDG+2D |
Voltage output | 20V |
Power supply | AC220V±10%% 50Hz/60Hz |
Working Environment | -10ºC-+40ºC RH≤85% |
- PRODUCT SHOW: